A cable consists of two main parts: The Conductor and the Insulation.
CONDUCTOR:
Conductors for Cables are drawn from electrolytic grade Copper / Aluminium to ensure compliance with global standards . Annealed conductors are bunched together on custom built heavy duty bunching machines to impart concrete shape to the conductor.
INSULATION:
Solid & Bunched conductors are insulated on ultra modern extrusion machines with high technology P.V.C. Compound, which ensures extra flexibility, ideally suited for conduit & concealed wiring. To manufacture multicore cables, the insulated cores are laid up to form a concentric shape. Inner cores are coded for identification as per National / International coding system or as per customer's specifications.
Outer sheathing is also provided with special soft PVC compound to minimize chances of electrical failures which may cause damage to expensive appliances, instruments & machinery etc.
QUALITY CONTROL:
Quality standards are in-built into every "Capital Cables" product Rigid tests and checks at every step, from raw material through manufacturing stages and finally up to the finished product ensure that "Capital Cables" products meet with international standards and therefore, consumer approval.
FLEXIBLE CABLES TECHNICAL DATA:
"Capital Cables" PVC insulated flexible single core, manufactured with bright annealed bare copper conductor for flexible use, insulated with Di- Electric grade PVC Compound. Impervious to oil, water, petrol, acids and greases generally for working voltage up to and included 1100 Volts.
|
| TECHNICAL DATA HEAVY DUTY FLEXIBLE CABLES |
|
CONDUCTOR |
INSULATION |
AREA |
NO. & SIZE OF WIRE |
DIAMETER
OF WIRE |
MAX.
RESISTANCE
AT 20°C |
DC OR SINGLE
PHASE AC
SEPARATE
IN AIR |
NOMINAL
THICKNESS |
NOMINAL
OVERALL
DIAMETER |
| SQ. MM. |
MM |
MM |
OHM/KM. |
AMPS. |
MM |
MM |
0.50 |
16/.2O |
0.95 |
37.50 |
4 |
0.6 |
2.30 |
0.75 |
24/.20 |
1.24 |
25.00 |
6 |
0.6 |
2.55 |
1.00 |
32/.20 |
1.31 |
18.70 |
10 |
0.6 |
2.70 |
1.50 |
48/.20 |
1.64 |
13.00 |
15 |
0.6 |
2.95 |
2.50 |
80/.20 |
2.08 |
7.98 |
20 |
0.7 |
3.65 |
4.00 |
128/.20 |
2.64 |
4.95 |
25 |
0.8 |
4.35 |
6.00 |
85/. 30 |
3.2 |
3.124 |
46 |
0.8 |
5.65 |
10.0 |
140/. 30 |
4.6 |
1.88 |
64 |
1.0 |
7.15 |
16.0 |
101/.45 |
5.9 |
1.140 |
85 |
1.4 |
8.95 |
25.0 |
168/.45 |
7.6 |
0.721 |
112 |
1.4 |
10.65 |
35.0 |
220/.45 |
8.7 |
0.525 |
138 |
1.4 |
11.75 |
50.0 |
325A45 |
10.6 |
0.362 |
172 |
1.6 |
14.05 |
70.0 |
440/.45 |
12.3 |
0.261 |
214 |
1.8 |
16.15 |
95.0 |
485/. 50 |
14.7 |
0.195 |
254 |
1.9 |
18.75 |
120.0 |
614/. 50 |
16.7 |
0.152 |
300 |
2.1 |
21.25 |
150.0 |
943A45 |
18.3 |
0.125 |
340 |
2.2 |
22.50 |
185.0 |
925/.50 |
20.3 |
0.101 |
390 |
2.5 |
25.50 |
240.0 |
1221/.50 |
23.0 |
0.076 |
460 |
2.5 |
28.50 |
|
|
| PVC INSULATED SOLID AND STRANED COPPER/ALUMINIUM CONDUCTOR CABLES FOR FIXED INSTALLATION WORKING VOLTAGE UPTO 1100VOLTS. |
|
CONDUCTOR |
INSULATION |
CROSS
SECTIONAL |
NO. & SIZE
OF WIRE |
COPPER C.R.
AT 20°C |
ALUMINIUM
CAPACITY
COPPER |
CURRENT
CARRYING
THICKNESS |
NOMINAL
THICKNESS OF
INSULATION |
NOMINAL
OVERALL
DIAMETER |
CU |
AL |
SQ. MM. |
MM. |
OHM / KM. |
OHM/KM. |
AMPS. |
AMPS. |
MM. |
MM. |
1.0 |
1/1.12 |
17.70 |
- |
18 |
- |
0.7 |
2.55 |
1.5 |
1/1.38 |
11.90 |
19.7 |
25 |
20 |
0.7 |
2.80 |
2.5 |
1/1.78 |
7.14 |
11.8 |
32 |
25 |
0.8 |
3.40 |
4.0 |
1/2.24 |
4.47 |
7.39 |
45 |
35 |
0.8 |
3.85 |
6.0 |
1/2.76 |
2.97 |
4.91 |
55 |
45 |
0.8 |
4.40 |
10.0 |
1/3.57 |
1.77 |
2.94 |
75 |
60 |
1.0 |
5.60 |
16.0 |
7/1.70 |
1.12 |
1.89 |
95 |
75 |
1.0 |
7.10 |
25.0 |
7/2.14 |
0.710 |
1.17 |
125 |
100 |
1.2 |
885 |
30.0 |
7/2.52 |
0.520 |
0.861 |
150 |
120 |
1.2 |
9.90 |
50.0 |
19/1.78 |
0.360 |
0.595 |
190 |
150 |
1.4 |
11.90 |
70.0 |
19/2.14 |
0.265 |
0.373 |
240 |
185 |
1.4 |
13.50 |
95.0 |
19/2.52 |
0.190 |
0.250 |
280 |
215 |
1.6 |
15.70 |
120.0 |
37/2.03 |
0.151 |
0.211 |
300 |
240 |
1.6 |
17.40 |
150.0 |
37/2.24 |
0.121 |
0.195 |
350 |
270 |
1.8 |
19.30 |
|
| TECHNICAL DATA FLEXIBLE MULTICORE ROUND |
|
CONDUCTOR |
INSULATION |
SHEATH |
OVERALL DIAMETER |
AREA |
NO. & SIZE OF WIRE |
DIAMETER |
RESISTANCE
AT 20°C |
CURRENT
CARRYING
CAPACITY |
THICKNESS
NOMINAL |
THICKNESS
NOMINAL |
2 CORE |
NOMINAL
3 CORE |
4 CORE |
SQ. MM |
MM |
MM |
OHM/KM. |
AMPS. |
MM |
MM |
MM |
MM |
MM |
0.50 |
16/.20 |
0.95 |
39.00 |
3 |
0.6 |
0.9 |
6.50 |
6.85 |
7.45 |
0.75 |
24/.20 |
1.24 |
26.00 |
6 |
0.6 |
0.9 |
7.00 |
7.40 |
8.05 |
1.00 |
32/.20 |
1.31 |
19.50 |
10 |
0.6 |
0.9 |
7.30 |
7.75 |
8.45 |
1.50 |
48/.20 |
1.64 |
13.00 |
15 |
0.6 |
0.9 |
7.80 |
8.25 |
9.25 |
2.50 |
80/.20 |
2.08 |
7.98 |
20 |
0.7 |
1.0 |
9.40 |
10.00 |
10.95 |
4.00 |
128/.20 |
2.64 |
4.95 |
25 |
0.8 |
1.0 |
10.75 |
11.50 |
12.65 |
|
|
| FLEXIBLE THREE AND FOUR CORE HEAVY DUTY CABLES FOR WORKING VOLTAGE 1100 VOLTS. |
|
CONDUCTOR |
INSULATION |
SHEATH |
OVERALL DIAMETER |
AREA |
NO. & SIZE OF WIRE |
DIAMETER |
RESISTANCE
AT 20°C |
CURRENT
CARRYING
CAPACITY |
THICKNESS
NOMINAL |
THICKNESS
NOMINAL |
2 CORE |
NOMINAL
3 CORE |
4 CORE |
SQ. MM |
MM |
MM |
OHM/KM. |
AMPS. |
MM |
MM |
MM |
MM |
MM |
0.50 |
16/.20 |
0.95 |
39.00 |
3 |
0.6 |
0.9 |
6.50 |
6.85 |
7.45 |
0.75 |
24/.20 |
1.24 |
26.00 |
6 |
0.6 |
0.9 |
7.00 |
7.40 |
8.05 |
1.00 |
32/.20 |
1.31 |
19.50 |
10 |
0.6 |
0.9 |
7.30 |
7.75 |
8.45 |
1.50 |
48/.20 |
1.64 |
13.00 |
15 |
0.6 |
0.9 |
7.80 |
8.25 |
9.25 |
2.50 |
80/.20 |
2.08 |
7.98 |
20 |
0.7 |
1.0 |
9.40 |
10.00 |
10.95 |
4.00 |
128/.20 |
2.64 |
4.95 |
25 |
0.8 |
1.0 |
10.75 |
11.50 |
12.65 |
|
|