Sl. No. |
Description |
3 x 16
+
1 x 16
+
1 x 25 |
3 x 25
+
1 x 16
+
1 x 25 |
3 x 50
+
1 x 16
+
1 x 25 |
3 x 50
+
1 x 16
+
1 x 35 |
3 x 70
+
1 x 16
+
1 x 50 |
3 x 95
+
1 x 16
+
1 x 70 |
3 x 120
+
1 x 16
+
1 x 70 |
| 1. |
Power/Neutral Core : |
|
|
|
|
|
|
|
| 1.1 |
Conductors |
|
|
|
|
|
|
|
| |
Nom. Cross sectional area
(i) Power cores (mm2)
(ii)Neutral cores (mm2) |
16
16 |
25
16 |
35
16 |
50
16 |
70
16 |
95
16 |
120
16 |
| |
Max. D.C. resistance conductor at 20ºC
(i) Power cores (Ohm/Km)
(ii)Neutral cores (Ohm/Km) |
1.91
1.91 |
1.20
1.91 |
0.868
0.910 |
0.641
0.910 |
0.443
0.910 |
0.320
1.910 |
0.253
1.910 |
| |
Approx. diameter of conductor
(i)Power cores (mm)
(ii)Neutral cores (mm) |
4.4
4.4 |
5.5
4.4 |
6.8
4.4 |
7.9
4.4 |
9.6
4.4 |
11.3
4.4 |
12.7
4.4 |
| 1.2 |
Insulation:
Minimum thickness:
(i)Power cores (mm)
(ii)Neutral cores (mm) |
1.0
1.0 |
1.0
1.0 |
1.0
1.0 |
1.2
1.0 |
1.4
1.0 |
1.4
1.0 |
1.6
1.0 |
2. |
Messenger Wire(Bare):
(i) Nom. Cross sectional area (Sq. mm)
(ii) Approx. Breaking load (KN) |
25
7.5 |
25
7.5 |
25
7.5 |
35
10.3 |
50
14.7 |
70
2.06 |
70
20.6 |
3. |
Current Rating:
Continuous current carrying
capacity of cable in Air at
Ambient temp. 40ºC (Amp.) |
51 |
70 |
86 |
105 |
130 |
155 |
180 |
4. |
Approx. weight (Kg./Km.) |
610 |
725 |
880 |
1270 |
1570 |
1180 |
1430 |
5. |
Number of Cores:
(i)Power cores
(ii)Neutral cores
(iii) Bare messenger |
(No.) : 3
(No.) : 1
(No.) : 1 |
6. |
De-rating factor
De-rating factors for variation in Air Temp.
Air Temp. (ºC) Rating Factor |
| 30 |
35 |
40 |
45 |
50 |
55 |
| 1.12 |
1.06 |
1.0 |
0.94 |
0.88 |
0.83 |
|
7. |
(i) Identification of power core :
(ii) Laying : |
By providing ridges on the insulation.
Three power cores and one Neutral core shall be suitable twisted around bare AAAC Messenger.
|
8. |
Detail of the Power / Neutral core :
(i) Conductor:
a) Material
(b) Flexibility class as per IS:8130/84
(c) Form of Conductor
(ii) Insulation:
(a) Material
(b) Colour of Insulation |
Aluminium to IS:8130/84
Class – 2
Compacted circular.
High Density Polyethylene to IS: 6474 - 1971
Black
|
9. |
Details of the Messenger wire (Bare)
(i) Material
(ii) Form of Conductor |
All Alloy Aluminium Conductor to IS:398 (IV).
Standard Compacted circular.
|